ARELPAN - W Drawer Type MCC Panels Panel systems have been designed to meet the requirements of industrial facilities, power plants, iron and steel production facilities and petrochemical facilities, refinery and treatment facilities in accordance to IEC standards. ARELPAN-C Panels have been tested by KEMA Independent LABs in Prague to ensure user safety as a priority. ARELPAN-C Panels, passing the tests successfully, were awarded with IEC 61439-1 & 2 Kema Full Type Test Certification.
Advantages
IEC 61439-1 & 2 Type Test Certificate in KEMA Labs
CONNECT-(Power Contact are Closed)
DISCONNECT-(Power Contact are Opened)
TEST-(Control Circuit Can Be Tested)
Contact modules was developed with Fraunhofer – Institute Germany laboratories
Full Size | Half Size | Quarter Size |
Up to 12 Modules Montage Capacity per Cabin Section
|
Up to 24 Modules Montage Capacity per Cabin Section
|
Up to 32 Modules Montage Capacity per Cabin Section
|
SELECTION TABLE FOR THE MCC DRAWER | |||||
Drawer Module Type | Max Module Montage Capacity per Cabin Section | Module Height | Module Width | Current Range | Number of available auxiliary contacts pin |
1/4 Quarter Size | 32 | 225 mm | 100 mm | 0-32 A | 32 |
1/2 Half Size | 24 | 150 mm | 220 mm | 0-50 A | 32 |
1/1 Full Size | 12 | 150 mm | 500 mm | 80-125 A | 32 |
6 | 300 mm | 500 mm | 160-250A | 32 | |
3 | 450 mm | 500 mm | 400-630A | 32 | |
3 | 600 mm | 500 mm | 400-630A | 32 |
- 630 A, Form 4b, IP41, 65kA
- Engine Control up to 300kW
- It is equipped with MECHANICAL INTERLOCK devices against operator errors.
- Mechanical coding is available, thus errors in different drawer type units are avoided (optional).
- There is PLUG & RUN system that enables Drawers to plug in and take out to the panel, by switching on/off their connections to energized main bus-bar. This process is applicable by each drawer modules as they are independent from each other.
- It passed ARK SAFETY test in accredited test laboratories
- Contact points are self-cleaning type when turning them ON position, thus no maintenance is required.
- It is possible to move power contacts when cables of power circuit is stable (Power cables should not be moved to avoid cable breaks.)
Innovative Pressure Contact
- Main switch can only be operated when the door is closed
- Cubicle door only opens in the disconnected position (can be overridden)
- Unit can only be withdrawn if the main switch is disconnected power-circuit are disconnected at coming and outgoing.
- Both withdrawable units and subsections can be excahnged or converted while the board is live.
- Mechanical encoding available (option).
- Coloured display showing the different positions of the drawer-unit
- Modular and Functional Design
- User Friendly Mechanism
- Arc Protection System
- Mechanical Safety Units
- Special Design Possibility
- Competitive Price and High Quality
PLUG & RUN securely with High Protection Contact Modules against ARC ERRORS!
- Each contact is insulated between the phases and against the earth. In case of overload, the ionized gases can’t short-circuit the two phases or with the earth.
- It provides the most economical quotation with the most appropriate dimensions according to the needs of your facility thanks to drawer units in different sizes.
- Energized bus-bar insulating against to bare hand touching with automated bus-bar shutting system (Shutter system)
- Phases between the vertical bus-bar section are fully insulated. It proves perfect protection even against strong dynamic loads.
Safety is a must!
- Master switch can only be activated when the door is closed
- It is possible to PLUG & RUN when master switch and units are disconnected
- It is possible to PLUG & RUN when there is energy in main bus-bars as units are independent of each other
- Mechanical coding is available, thus errors are avoided in different drawer type units (optional)
- It is equipped with strong MECHANICAL INTERLOCK devices against operator errors
Standard Information
Rated Current, In
6300 A
Internal Arc Test
65kA , 300 ms
Protection Class
IP41
Forming
Up to form 4b
Standard Color
RAL 7035, Elektrostatik
Carcass Material Type
Galvaniz
Distribution System
TN-C, TN-S, TN C-S, TT, IT
Operating Voltage, Ue
Up to 690 V
Impact Resistance Voltage, Uimp
8kV / 12kV
Ambient Temperature
35 C (24h)
Safety is a must!
- Strong Profile Structure
- Modular Mechanical Assembly Units
- Mounting Types are Available For All Brands
- 2 mm Galvanized Steel, RAL 7035 Colour
- Stylish and Arty Outlook